TENSE phase protection relay - adjustable asymmetry 5-50%

The phase protection relay from TENSE (Turkey) is designed to protect three-phase electric motors and other three-phase equipment from power supply network faults. The device checks the correct phase sequence, phase asymmetry, undervoltage, overvoltage, and ensures safe disconnection of the load when set limits are exceeded.

The wide range of settings makes the relay suitable for most industrial and commercial applications, especially when precise and stable motor protection is required.

Main features

  • Phase sequence control - protection against incorrect connections.

  • Adjustable asymmetry: 5% - 50%.

  • Adjustable undervoltage: 260-360 VAC.

  • Adjustable overvoltage: 400-480 VAC.

  • Adjustable error delay time (Err In): 1-30 s.

  • Adjustable recovery time (Err OUT): 1-30 s.

  • Clear indication on the 3×3 segment display.

  • High accuracy and fast response to network faults.

  • Standard DIN rail mounting.

Operating principles

Normal operation

When all phase voltages are within limits and the phase sequence is correct:

  • the relay trips,

  • The OUT LED lights up.

High voltage error (H)

  • If the phase exceeds the set limit → the Err In time is pending, H is displayed.

  • The relay switches off, OUT turns off.

  • When 5 V drops below the set value, Err OUT starts, the relay switches on again.

Low voltage error (L)

  • Drop below the set limit → Err Em waiting, L is displayed.

  • The relay switches off.

  • When voltage rises 5 V above the threshold → Err OUT waiting, the relay activates.

Phase asymmetry (Asy)

  • If the voltage difference between phases exceeds the set threshold (5-50%):

    • ASy is displayed after the Err In time, the relay is deactivated.

  • When asymmetry is reduced to less than (set threshold - 2%) → wait time Err OUT, the relay switches on.

Phase sequence error (pHs)

  • When a phase sequence error occurs, the relay waits for Err In and then displays pHs.

  • The relay switches off and remains off until the correct sequence is restored.

  • After the phase sequence is corrected, Err OUT occurs and the relay switches on.


Technical parameters

Parameter Parameter value
Operating voltage (Un) 3×380 V AC + N
Frequency 50/60 Hz
Power input < 6 VA
Ambient temperature -20 °C to +55 °C
High voltage threshold 400-480 V AC
Low voltage threshold 260-360 V AC
Asymmetry 5-50% (adjustable)
Error time (Err In) 1-30 s
Reset time (Err OUT) 1-30 s
Relay contact 5 A / 250 V AC (resistive load)
Display 3×3 segments, 1 LED
Mounting DIN rail
Weight < 150 g
Maximum installation height < 2000 m
Cable cross-section up to 2.5 mm²

Manual